Stability Analysis of Hydropower Generators
2026 (English)Independent thesis Advanced level (professional degree), 20 credits / 30 HE credits
Student thesis
Abstract [en]
One of the crucial components of a hydropower unit is the generator. It is responsible for converting mechanical energy into electrical energy. One of the parameters used to evaluate new or potential upgrades for generators is generator stability. It is described as the point in which the restoring mechanical forces of the unit are less than the forces which destabilises the unit, the largest contributor of which are the magnetic pull forces. This magnetic pull force is referred to as the unbalanced magnetic pull (UMP). Currently, in the industry the most common approach is to use a beam element model of the unit, with varying complexity, e.g. either linear or non-linear bearings and magnetic pull formulation. The aim of the thesis is to create a 3D-model for stability analysis and investigate the impact of cases such as centrifugal loads and forces and moments from the turbine runner. In addition, other versions were created with a stiff generator and both a stiff generator and rotor to verify and compare against other developed models, one of which was a model similar to the ones used in the industry. Two different formulations of the UMP was studied and used, the pole force formulation and the UMP formulation. The 3D-model of the unit used a simplified generator model, where the rotor rim and poles were fully modelled along with the connection plates. This was then connected to a rotor, represented by beam elements and supported by bearings and their support structure. The other created model used the same model for the rotor and bearing model as for the 3D-model.
From the analysis it was evident that centrifugal loads reduced the stability substantially for the unit. In particular, the influence of compliant upper bearing supports were shown to reduce the stability threshold substantially. Comparing the stiff generator cases against the flexible case, there was a significant difference in the stability and how the UMP increased with increased eccentricity. This was due to the expansion of the generator, which caused it to ovalise slightly. The two used formulations agreed well until an eccentricity over half of the nominal air-gap, after which the pole force formulation diverged greatly.
Place, publisher, year, edition, pages
2026. , p. 41
Keywords [en]
Hydropower, Generator Stability, Finite Element Analysis, Unbalanced Magnetic Pull, Nonlinear Statics
National Category
Applied Mechanics
Identifiers
URN: urn:nbn:se:ltu:diva-117974OAI: oai:DiVA.org:ltu-117974DiVA, id: diva2:2067655
Educational program
Mechanical Engineering, master's level
Supervisors
Examiners
2026-06-102026-06-082026-06-10Bibliographically approved