Systemanalys av kylteknik i läkemedelsindustri: Identifiering och utvärdering av kylsystem som alternativ till älvvattenkylning
Karlstad University, Faculty of Health, Science and Technology (starting 2013).
2025 (Swedish)Independent thesis Advanced level (degree of Master (Two Years)), 20 credits / 30 HE creditsStudent thesisAlternative title
System Analysis of Cooling Technologies in the Pharmaceutical Industry : Identification and Evaluation of Cooling Systems as Alternatives to River Water Cooling (English)
Abstract [sv]

Denna studie undersöker tekniska lösningar för att ersätta ett befintligt öppet

älvvattenbaserat kylsystem med ett internt cirkulerande kylsystem vid ett

läkemedelsföretag i Karlskoga. Företaget använder idag ett kylsystem där älvvatten

utgör kylmedium, vilket skapar utmaningar relaterade till korrosion, avlagringar,

biologisk påväxt samt variationer i kylkapacitet beroende på säsongsrelaterade

temperaturförändringar i älvvattnet. Det öppna systemet medför därmed inte bara

ineffektiv kylning och höga underhållskostnader utan också en betydande

resursförbrukning och potentiella driftstörningar.

En översikt ges över internt cirkulerande kylsystem som ett effektivare alternativ

till öppna kylsystem med naturvatten som värmesänka, med fokus på förbättrad

kontroll av kylprocessen, minskade problem med fouling och korrision samt lägre

miljöpåverkan på grund av att behovet av kontinuerligt intag av naturligt vatten

elimineras.

En detaljerad analys och modellering har utförts med hjälp av

beräkningsverkstyget Simulink för att simulera olika tekniska alternativ för

uppbyggnaden av ett nytt kylsystem. Målet med studien är att identifiera det optimala

kylsystemet ur ett ekonomiskt, resursanvändnings och miljömässigt perspektiv.

Analysen omfattar olika systemsammansättningar med komponenterna, torrt

kyltorn, öppet kyltorn, ackumulatortank, kompressordriven kylmaskin,

absorptionskylmaskin samt möjligheten till inköp av kommunalt vatten som

stödsystem. De undersökta systemen har utvärderats på studiens nyckeltal;

livscykelkostnad (LCC), vattenanvändning per år samt alstring av

koldioxidekvivalenter per år.

Kylbehovet för de olika systemsammasättningarna utgick ifrån en analys av

värmen som det befintliga älvvattensystemet avleder från processerna under två

valda produktionskampanjer, för beskriva ett sommarfall och ett vinterfall.

Analyserna över de olika systemsammansättningarna började med att studera

trender på hur kostnaden, vattenanvändning och alstring av koldioxidekvivalenter

varierar beroende på den dimensionerande temperaturen i kylkretsen samt

dimensionerna på komponenterna under sommarfallet. Efter kartläggningen av

trenderna valdes fem systemlösningar ut för att genomgå årsberäkningar där

sommarfallet och vinterfallet växelvis upprepades för att representera ett kylbehov

över ett år på 3995 MWh, i syfte att ta fram nyckeltalen för respektive system.

Resultaten visar att den dominerande temperaturen i kylkretsen är en avgörande

faktor på kylsystemets uppbyggnad och nyckeltalen, då temperaturen avgör när

kyltornet kan vara aktivt och kan leverera tillräckligt med kyla. Systemet med öppet

kyltorn på 2000 m2 (800 kW) och stödsystem presenterar lägst livscykelkostnader,

1,37 miljoner SEK för en dimensionerande temperatur på 18°C och 909 tusen SEK

för 22°C, samt låga utsläpp av koldioxidekvivalenter. Detta alternativ innebär dock

en hög vattenanvändning på 8159 m3/år för en dimensionerande temperatur på 18°C

och 1008 m3/år för en temperatur på 22°C. Om vattenanvändningen prioriteras är

kombinationen av ett öppet kyltorn och en kompressordriven kylmaskin (800 kW)

det ekonomiskt gynnsammaste alternativet vid en dimensionerande temperatur på

18°C. Vid en högre temperatur på 22°C är systemet med öppet kyltorn och enackumulatortank på 500 m3 som täcker kylbehoven under perioder då kyltornet är

inaktivt ekonomiskt gynnsammast. Dessa lösningar minskar vattenanvändningen

med 87,9% för den dimensionerande temperaturen i kylkretsen på 18°C samt 30,9%

för 22°C, men medför en ökad livscykelkostnad med en faktor på 5,6 för 18°C och

2,4 för 22°C.

Sammanfattningsvis visar studien att det optimala systemet ur ett ekonomiskt

perspektiv bygger på en balanserad kombination av komponenter med låg

investeringskostnad och låg driftkostnad. Valet av högsta tillåtna temperatur i

processen är avgörande för hur kylsystemets konfiguration och dimensionering bör

utformas, och har därmed en direkt inverkan på systemets prestanda i form av

livscykelkostnad, vattenanvändning och klimatpåverkan. En högre tillåten

temperatur i processen resulterar i lägre värden för studiens nyckeltal.

Abstract [en]

This study investigates technical solutions for replacing an existing open river-

water-based cooling system with an internally circulated cooling system at a

pharmaceutical company in Karlskoga, Sweden. The current system uses river water

and municipal water as cooling media, which leads to challenges related to corrosion,

scaling, biological fouling, and variations in cooling capacity due to seasonal

temperature fluctuations in the river. Consequently, the open system results in not

only inefficient cooling and high maintenance costs, but also significant resource

consumption and potential operational disruptions that can affect product quality and

production stability.

An overview is provided of internally circulated cooling systems as a more

efficient alternative to open systems using natural water as a heat sink. The focus is

on improved control of the cooling process, reduced fouling and corrosions issues,

and lower environmental impact by eliminating the need for continues intake of

natural water.

A detailed analysis and modeling have been carried out using the simulation tool

Simulink to simulate different technical alternatives for configuring a new cooling

system. The objective of the study is to identify the optimal system from economic,

resource consumption, and environmental perspectives. The analysis includes

various system configurations combining components such as dry cooling towers,

open wet cooling towers, accumulator tanks, compressor-driven chillers, absorption,

and the option to purchase municipal water as a support system. The systems were

evaluated based on the study´s key performance indicators: life cycle cost (LCC),

annual water consumption, and annual generation of carbon dioxide equivalents.

The cooling demand for the different configurations was based on an analysis of

the heat removed by the existing river water system from the processes during two

selected production campaigns, representing a summer and a winter case.

The analysis began with studying trends in how cost, water consumption, and

emissions of carbon dioxide equivalents vary depending on the design temperature

of the cooling circuit and the size of the components during the summer case. Based

on this trend analysis, five system solutions were selected for full-year calculations.

The summer and winter cases were alternated repeatedly to represent an annual

cooling demand of 3995 MWh, which formed the basis for calculating the key

performance indicators for each system.

The results show that the dominant temperature in the cooling circuit is a decisive

factor in system design and the performance indicators, as it determines when the

cooling tower can operate and provide sufficient cooling. The system with an open

cooling tower of 2000 m2 (800 kW) and a support system presented the lowest life

cycle costs: 1,37 million SEK for a design temperature of 18°C and 909 thousand

SEK for 22°C for a design temperature of 22°C, as well as low emissions of carbon

dioxide equivalents. However, this solution involves high water consumption: 8157

m3/year at 18°C and 1008 m3/year at 22°C. If water consumption is prioritized, the

most economically favorable solution at 18°C is a combination of an open cooling

tower and a compressor-driven chiller (800 kW). At a higher temperature of 22°C,

the most favorable system is an open cooling tower with a 500 m3 accumulator tankthat covers the cooling demand during periods when the tower is inactive. These

solutions reduce water consumption by 87,9% at 18°C and 30,9% at 22°C, but

increase the life cycle cost by a factor of 5,6 for 18°C and 2,4 for 22°C.

In conclusion, the study shows that the optimal system from an economic

perspective is based on a balance combination of components with low investment

and operating costs. The choice of maximum allowable process temperature is

critical in determining the configuration and dimensioning of the cooling system and

has direct impact on its performance in terms of life cycle cost, water use, and climate

impact. A higher allowable temperature results in lower values for the study´s key

indicators.

Place, publisher, year, edition, pages
2025. , p. 57
Keywords [en]
accumulator tank, chiller, cooling system, cooling tower
Keywords [sv]
ackumulatortank, kylmaskin, kylsystem, kyltorn
National Category
Energy Systems
Identifiers
URN: urn:nbn:se:kau:diva-106138OAI: oai:DiVA.org:kau-106138DiVA, id: diva2:1981054
External cooperation
Sweco
Subject / course
Environmental and Energy Systems
Educational program
Engineering: Energy and Environmental Engineering (300 ECTS credits)
Supervisors
Examiners
Available from: 2025-08-11 Created: 2025-07-03 Last updated: 2026-02-12Bibliographically approved

Open Access in DiVA

Systemanalys av kylteknik i läkemedelsindustri(2489 kB)109 downloads
File information
File name FULLTEXT01.pdfFile size 2489 kBChecksum SHA-512
5f629ece5858b4cbb83996253ba248fa357b8e5e93390d640e528cfd6e48da0278daeee8a58ee79ecda2516e838b87e1434c9850ff4201e013a9921d1ab67208
Type fulltextMimetype application/pdf

By organisation
Faculty of Health, Science and Technology (starting 2013)
Energy Systems

Search outside of DiVA

GoogleGoogle Scholar
Total: 111 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 120 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf