Field measurements of supermarket refrigeration systems. Part II: Analysis of HFC refrigeration systems and comparison to CO2 trans-critical
KTH, School of Industrial Engineering and Management (ITM), Energy Technology, Applied Thermodynamics and Refrigeration.
KTH, School of Industrial Engineering and Management (ITM), Energy Technology, Applied Thermodynamics and Refrigeration.
KTH, School of Engineering Sciences (SCI), Physics, Nuclear Power Safety.
Show others and affiliations
2017 (English)In: Applied Thermal Engineering, ISSN 1359-4311, E-ISSN 1873-5606, Vol. 111, no 1, 170-182 p.Article in journal (Refereed) Published
Abstract [en]

This part of the study investigates the performance of HFC refrigeration systems for supermarkets and compares the performance with alternative CO2 trans-critical solutions. The investigated HFC system solutions are typical in supermarkets in Sweden. The analysis in this study is based on field measurements which were carried out in three supermarkets in Sweden. The results are compared to the findings from Part I of this study where five CO2 trans-critical systems were analyzed. Using the field measurements, low and medium temperature level cooling demands and COP’s are calculated for five-minute intervals, filtered and averaged to monthly values. The different refrigeration systems are made comparable by looking at the different COP’s versus condensing temperatures. The field measurement analysis is combined with theoretical modelling where the annual energy use of the HFC and CO2 trans-critical refrigeration systems is calculated. Comparing the field measurement and modelling results of COP’s for HFC and CO2 systems, the new CO2 systems have higher total COP than HFC systems for outdoor temperatures lower than about 24 C. The modelling is used to calculate the annual energy use of HFC and new CO2 system in an average size supermarket in Stockholm, new CO2 systems use about 20% less energy than a typical HFC system. The detailed analysis done in this study (Part I and Part II) proves that new CO2 trans-critical refrigeration systems are more energy efficient solutions for supermarkets than typical HFC systems in Sweden.

Place, publisher, year, edition, pages
Elsevier, 2017. Vol. 111, no 1, 170-182 p.
National Category
Energy Engineering
URN: urn:nbn:se:kth:diva-193111DOI: 10.1016/j.applthermaleng.2016.09.073OAI: diva2:975212

QC 20161005

Available from: 2016-09-29 Created: 2016-09-29 Last updated: 2016-10-27Bibliographically approved

Open Access in DiVA

fulltext(2989 kB)8 downloads
File information
File name FULLTEXT01.pdfFile size 2989 kBChecksum SHA-512
Type fulltextMimetype application/pdf

Other links

Publisher's full text

Search in DiVA

By author/editor
Sawalha, SamerPiscopiello, SalvatoreKarampour, MazyarManickam, LouisRogstam, Jörgen
By organisation
Applied Thermodynamics and RefrigerationKTHNuclear Power Safety
In the same journal
Applied Thermal Engineering
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 8 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Altmetric score

Total: 28 hits
ReferencesLink to record
Permanent link

Direct link