Handlingsplan för ägare av transformatorer med korrosiv olja
Umeå University, Faculty of Science and Technology, Department of Applied Physics and Electronics.
2016 (Swedish)Independent thesis Basic level (university diploma), 10 credits / 15 HE creditsStudent thesis
Abstract [sv]

Sedan början av 2000-talet har ett stort antal transformatorer havererat av en initialt, okänd anledning. Problemet visade sig vara att en antioxidationstillsats i oljan, dibensyl disulfid (DBDS), reagerat med kopparen i lindningarna och vilket gett upphov till avlagringar på isolationspapperet i form av kopparsulfid. Kopparsulfiden i sin tur försvagade papperets isolationsförmåga och allvarliga driftstörningar eller driftstopp på grund av kortslutningar kan ske. Ett stort antal studier har genomförts för att ge klarhet i vad som händer, varför det händer och vad man kan göra åt problemet. Bakgrunden till detta examensarbete är att en 230MVA transformator har, trots att ägaren vidtagit rekommenderade försiktighetsåtgärder, havererat. Denna studie visar att ett flertal faktorer, såsom värme, svavelhalt och dåliga skarvar i lindningarna, påskyndar korrosionen av koppar och bildandet av kopparsulfid. Riskerna för haveri kan minskas genom att tillsätta Irgamet 39 i ett tidigt skede eller genom att byta/avsvavla oljan om transformatorn är äldre. Den redan bildade kopparsulfiden går däremot inte att avlägsna, så ett viktigt första steg är att stärka det elektriska skyddet genom att se över avledarna på transformatorn

Abstract [en]

Since the early 2000 a great number of transformers have broken down, without any apparent reason at first. The problem was identified to be an anti-oxidization-additive in the oil, dibenzyl disufide (DBDS), that had reacted with the copper in the windings. This gave rise to copper sulfide deposits on the isolating paper, which in turn reduced the isolating properties of the paper. A large number of studies have been completed to clarify what’s happening, why it’s happening and what can be done about it. The background for this thesis is that a 230MVA transformer broke down, despite the fact that the owner had taken the recommended precautions. This study will show that a number of factors, such as heat, Sulphur content and bad joints in the windings can accelerated the corrosion of copper and the formation of copper sulfide. The risks of a break-down can be reduced by adding Irgamet 39 at an early stage or by an oil change/desulphurization if the transformer is older. The already formed copper sulfide, on the other hand, cannot be removed and so an important first step is to fortify the electrical protection of the transformer by looking over the surge-arresters.

Place, publisher, year, edition, pages
2016. , 29 p.
Series
EL, 1613
Keyword [sv]
DBDS, kopparsulfid, dibensyl disulfid
National Category
Engineering and Technology
Identifiers
URN: urn:nbn:se:umu:diva-122436OAI: oai:DiVA.org:umu-122436DiVA: diva2:938899
External cooperation
Vattenfall
Educational program
Högskoleingenjörsprogrammet i Elkraftteknik - nätbaserat
Supervisors
Examiners
Available from: 2016-06-17 Created: 2016-06-17 Last updated: 2016-06-17Bibliographically approved