Selektivplan för 70/20 kV transformatorstation
Umeå University, Faculty of Science and Technology, Department of Applied Physics and Electronics.
2015 (Swedish)Independent thesis Basic level (professional degree), 10 credits / 15 HE creditsStudent thesisAlternative title
Selectivity coordination for a 70/20 kV transformer station (English)
Abstract [sv]

Detta examensarbete har utförts på uppdrag av Sandviken Energi Elnät AB, i syfte att kontrollera och uppdatera selektivplanerna för en utav deras mottagningsstationer. Tidigare reläskyddsinställningar för stationerna på nätet är något som följt med sedan gammalt och insyn i huruvida dessa stämt överens med de verkliga förhållandena har saknats.

Data för arbetet har samlats in främst från Sandviken Energis kartsystem Meldis vad gäller ledningslängder, transformatordata och underliggande nät. Data har även samlats in från tidigare selektivplansberäkningar på det aktuella nätet samt de aktuella reläskyddsinställningarna.

I arbetet så förklaras de grundläggande principerna för reläskyddsteori, aktuella regler och standarder inom ämnet samt grundprinciperna för selektivitet. Arbetet förklarar även de beräkningar som behöver genomföras för att kunna ta fram styrparameterar att använda vid framtagning utav reläskyddsinställningar.

Beräkningar för kortslutningsströmmar i nätet har skett enligt SS-EN 60909-0 och har genomförts i Excel. Utifrån de framräknade maximala och minimala kortslutningsströmmar, samt insamlad data över nätet har ett förslag för nya reläskyddsinställningar tagits fram. Dessa sammanställs i log-log diagram för att kunna ge en snabb överblick av selektiviteten i anläggningar samt en tabell med samtliga inställningar.

Resultatet visar på att de tidigare reläskyddsinställningarna uppvisar brister, då kortslutningsinställningarna i vissa fall skiljt sig mer än 1000 ampere mot för lägsta förekommande kortslutningsströmmar. De framtagna inställningsförslagen kan dock inte tillämpas direkt, då resultaten pekar på att liknande fel förekommer i underliggande stationer, vilket behöver ses över innan nya inställningar kan implementeras.

Abstract [en]

This thesis project has been carried out on behalf of Sandviken Energi Elnät AB, in oder to verify and update the selectivity coordination for one of their receiving stations. Current settings for the relay protection system in the station is mostly old settings, inherited since old, and Sandviken Energi has been lacking insight into whether the settings are consistent with regard to the actual conditions in the network.

Data has been collected mainly from Sandviken Energi’s GIS-system, Meldis in terms of line lengths, transformer data and details about the underlying network. Data has also been collected from previous coordination calculations as well as the current relay settings.

In the project the basic principles of relay protections theory, current laws, regulations and standards on the subject as well as basic selectivity principles are explained. The project also details the calculations that must be performed in order to produce relevant control parameters to use when detailing the settings for the protective relays.

Calculations of the short-circuit currents in the network has been made in accordance with SS-EN 60909-0 and has been implemented using Excel. Based on the calculated maximum and minimum short-circuit currents as well as the previously collected network data, a draft for new relay settings has been developed. These settings are compiled in log-log graphs over current and time to provide a quick overview of the selectivity coordination in the facilities as well as a table containing a list of all proposed settings.

The results of the project indicate that the previous relay settings are inadequate, as the short-circuit settings in some cases differ more than 1000 amperes from the lowest occurring short-circuit currents. However, the proposed settings cannot be applied immediately as the results also indicated that similar errors exists in the underlying stations as well, which needs to be reviewed before implementing changes to ensure proper protective function. 

Place, publisher, year, edition, pages
2015. , 20 p.
Series
EL, 1510
Keyword [sv]
Reläskydd, selektivplan, kortslutning, selektivitet
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
URN: urn:nbn:se:umu:diva-104535OAI: oai:DiVA.org:umu-104535DiVA: diva2:820168
External cooperation
Sandviken Energi Elnät AB
Educational program
Högskoleingenjörsprogrammet i Elkraftteknik - nätbaserat
Presentation
, Umea
Supervisors
Examiners
Available from: 2015-06-18 Created: 2015-06-11 Last updated: 2015-06-18Bibliographically approved

Open Access in DiVA

fulltext(988 kB)307 downloads
File information
File name FULLTEXT01.pdfFile size 988 kBChecksum SHA-512
c21026fe703d3cf60454450279198a19bea73dbb97dbb6a7283d29802c20f8eeba8e8f6a63e033bcb57018c27a743e681ef8e8fb7e03cf7571eb66e4f9ffaba2
Type fulltextMimetype application/pdf

By organisation
Department of Applied Physics and Electronics
Electrical Engineering, Electronic Engineering, Information Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 307 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 692 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf