Experimentella studier av värmeflöden och värmelagring i ett bebott flerbostadshus
Umeå University, Faculty of Science and Technology, Department of Physics.
1987 (Swedish)Doctoral thesis, monograph (Other academic)Alternative title
Experimental studies of heat flow and heat storage in an occupied apartment building (English)
Abstract [en]

The study is experimentally inclined, with a high target precision for performance measurement. A comprehensive programme of measurements was carried out in a two-storey building, having a massive structure and dating from 1970. Measurements were made continuously during the heating season from a total of about 70 points. Readings were taken every 30 seconds, and the mean values stored in a computer every 15 minutes.

Analysis of the results have been concentrated on:

* Thermal inertia, and particularly that of cooling mechanisms.

* Time delays in heat flows through the building envelope in response to variations in ambient temperature.

* The amount of solar input beneficially retained when operating with night setback and with normal operation.

The results indicate that the building has both a long time constant, of about 200 h, and a short one, of about 1.5 h. The magnitude of the shorter time constant depends on the thermal capacity of the interior of the building (furniture, curtains etc.), and can be regarded as having some validity for other apartment building stock.

Analyses of temperature gradients in the internal surfaces of the exterior walls indicate that the building's ventilation system, which was originally constructed as an exhaust air ventilation system, but with the inflow of fresh air blocked off, generates a dynamic insulation effect. Calculations indicate that this effect can provide a saving of 6 % of the total heating requirement, excluding that for domestic hot water.

Investigation of the static heat requirement with and without night set-back indicate a considerable potential annual saving of heating energy, amounting to a maximum of 13 %, provided that the building is heated in accordance with a prescribed strategy. A 'comfort indoor temperature' has also been determined, being the temperature above which the occupants of the building consume excessive heating energy.

Theoretical models have been derived to illustrate the short time constant and to analyse the dynamic insulation effect noted.

Place, publisher, year, edition, pages
Umeå: Umeå universitet , 1987. , 161 p.
Keyword [en]
Energy balance, heat storage, heat flow, night setback, buildings, time constants
National Category
Physical Sciences
URN: urn:nbn:se:umu:diva-100376ISBN: 91-7174-282-4OAI: diva2:792510
Public defence
1987-04-03, Fysiska institutionen, hörsal D LU 0, Umeå universitet, Umeå, 10:00

Diss. Umeå : Umeå universitet, 1987

Available from: 2015-03-04 Created: 2015-03-02 Last updated: 2015-04-10Bibliographically approved

Open Access in DiVA

fulltext(6435 kB)56 downloads
File information
File name FULLTEXT01.pdfFile size 6435 kBChecksum SHA-512
Type fulltextMimetype application/pdf

Search in DiVA

By author/editor
Stenlund, Lars
By organisation
Department of Physics
Physical Sciences

Search outside of DiVA

GoogleGoogle Scholar
Total: 56 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 102 hits
ReferencesLink to record
Permanent link

Direct link