Change search
ReferencesLink to record
Permanent link

Direct link
Smarter Fault Localization in Distribution Systems: A Self-Sustained Sensor for Current Measurement
Norwegian University of Science and Technology, Faculty of Information Technology, Mathematics and Electrical Engineering, Department of Electrical Power Engineering.
2014 (English)MasteroppgaveStudent thesis
Abstract [en]

This thesis deals with the development of self-sustained sensors based on non-conventional measurement techniques. The motivation behind this topic is to help utility companies reduce their fault handling time and improve the way faults are handled. As of today, the distribution system does not have widespread surveillance and automation systems in place. The thesis therefore investigates a sensor design based on Rogowski coils (RC), with both measurement and power supply capabilities. The concept of printed-circuit-board Rogowski coils (PCB RC) and conventional RCs for current measurement is presented. A theoretical, dimensional study with respect to feasibility and output signal magnitude is then performed. On basis of this analysis, a PCB RC prototype is manufactured. For the sensor to be implemented in the resonance grounded distribution system, it must be able to measure currents of low magnitude, as the fault current is compensated by Petersen coils. The prototype is therefore tested for common distribution system current values. Due to limitations during construction and design flaws, the PCB RC performance was poor. The induced voltage error, with respect to the theoretical response was 64.3 - 69.1 %. As the prototype's ability to supply enough power to the sensor circuitry (demand found to be > 10 mW) proved so limited, a more thorough analysis concerning the RC is presented. Obtaining this amount of power is, theoretically possible and easier with a conventional RC. Its maximum average power supply capability was found to be 10.4 mW during ideal conditions. Even better results can probably be obtained as well. Based on this RC, the complete sensor system is discussed. This include rectification, digitizing, integration and boosting of the RC voltage to 3 V for battery application. A survey of possible fault localization methods for resonance grounded distribution systems is presented and an implementation is suggested. Finally, the prototype is tested with short circuit currents of 30 kA amplitude. The performance was better than for the load current test, but the magnitude error was still substantial. It varied from 20 % to 40 %. However, the lab's signal integration showed that the prototype reproduced the applied current waveform accurately. The simulations, testing and analysis performed indicate that a RC can be used for both supply of power and measurements. However, a prototype should be manufactured in order to assess this thesis' theoretical results. Combined with the proposed auxiliary circuitry and implementation strategy, it can improve the utility's fault handling.

Place, publisher, year, edition, pages
Institutt for elkraftteknikk , 2014. , 147 p.
Keyword [no]
ntnudaim:11742, MTENERG energi og miljø, Elektrisk energiteknikk
URN: urn:nbn:no:ntnu:diva-27227Local ID: ntnudaim:11742OAI: diva2:762900
Available from: 2014-11-13 Created: 2014-11-13

Open Access in DiVA

fulltext(63191 kB)777 downloads
File information
File name FULLTEXT01.pdfFile size 63191 kBChecksum SHA-512
Type fulltextMimetype application/pdf
cover(184 kB)6 downloads
File information
File name COVER01.pdfFile size 184 kBChecksum SHA-512
Type coverMimetype application/pdf
attachment(19344 kB)25 downloads
File information
File name ATTACHMENT01.zipFile size 19344 kBChecksum SHA-512
Type attachmentMimetype application/zip

By organisation
Department of Electrical Power Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 777 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 110 hits
ReferencesLink to record
Permanent link