Change search
ReferencesLink to record
Permanent link

Direct link
Analysis of heat recovery in supermarket refrigeration system using carbon dioxide as refrigerant
KTH, School of Industrial Engineering and Management (ITM), Energy Technology, Applied Thermodynamics and Refrigeration.
2014 (English)Independent thesis Advanced level (degree of Master (Two Years)), 20 credits / 30 HE creditsStudent thesis
Abstract [en]

The aim of this study is to investigate the heat recovery potential in supermarket refrigeration systems using CO2 as refrigerants. The theoretical control strategy to recover heating demand from refrigeration system is explained thoroughly and the heat recovery process from two existing supermarket using CO2 booster units is analyzed and evaluated. The measured data of refrigeration systems is obtained through Iwmac interface, processed using Excel and Refprop. The aim is to see what control strategy is used in these systems and weather it matches the theoretical one and at what level heat is recovered from the system.

Besides, a simulation model is made by EES to investigate the potential of higher rate of heat recovery in the supermarkets. The simulation results are compared with field measurement and validated by measured values. Then, the ability of refrigeration system to do heat recovery at quite high rates for covering the total heating demand without using parallel heating system is evaluated and efficiency of the system is calculated. At the next step the heat recovery potential at other refrigeration solutions such as R404A conventional and CO2-ammonia cascade systems are studied and the results are compared to booster units. Finally, the potential for selling heat from the refrigeration system in supermarket to district heating network is investigated. Two different scenarios are made for such purpose and the results are evaluated.

The heat recovery control strategy of existing supermarkets does not match the theoretical strategy and regarding the capacity of the system, heat is recovered to low extent. Simulation shows that heat can be recovered to higher extent at quite high heating COP of 3-5. Additionally the other heat recovery solutions for R404A conventional and CO2-ammonia cascade systems are found to be competitive to CO2 booster system.  The analysis of selling heat to district heating network shows that CO2 booster system is capable of covering the demand at reasonable heating COP as the first priority and selling the rest to district heating network at heating COP of 2 as second priority.  

Place, publisher, year, edition, pages
Keyword [en]
Supermarket refrigeration, heat recovery, carbon dioxide
National Category
Energy Engineering
URN: urn:nbn:se:kth:diva-148668OAI: diva2:736948
Educational program
Master of Science - Sustainable Energy Engineering
Available from: 2014-08-25 Created: 2014-08-11 Last updated: 2014-08-25Bibliographically approved

Open Access in DiVA

fulltext(6122 kB)771 downloads
File information
File name FULLTEXT01.pdfFile size 6122 kBChecksum SHA-512
Type fulltextMimetype application/pdf

By organisation
Applied Thermodynamics and Refrigeration
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 771 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 547 hits
ReferencesLink to record
Permanent link

Direct link