Dynamic line rating implementation as an approach to handle wind power integration: A feasibility analysis in a sub-transmission system owned by Fortum Distribution AB
KTH, School of Electrical Engineering (EES), Electromagnetic Engineering. (RCAM)
2013 (English)Independent thesis Advanced level (degree of Master (Two Years)), 20 credits / 30 HE creditsStudent thesis
Abstract [en]

Based on conventional static line rating method, the actual current carrying capability of overheadconductors cannot be judged. Due to continuous increment in electricity demand and the difficultiesassociated with new line constructions, the overhead lines are therefore required to be rated based on amethod that should establish their real-time capability in terms of electricity transmission. The methodused to determine the real-time ampacity of overhead conductors not only can enhance their transmissioncapacity but can also help in allowing excessive renewable generation in the electricity network. In thisdiploma work, the issues related to analyzing an impact of wind power on periodical loading of overheadline as well as finding its static and dynamic ampacities with line current are investigated in detail.Initially, in this project, the investigation related to finding a suitable location for the construction of a 60MW wind farm is taken on board. Thereafter, the wind park is integrated with a regional grid, owned byFortum Distribution AB. In addition to that, the electricity generated from the wind park is also calculatedin this project. Later on, the work is devoted to finding the static and dynamic line ratings for‘VL3’overhead conductor by using IEEE-738-2006 standard.Furthermore, the project also deals with finding the line current and making its comparison withmaximum capacity of overhead conductor (VL3) for loading it in such a way that no any violation of safeground clearance requirements is observed at all. Besides, the line current, knowing the conductortemperature when it transmits the required electricity in the presence of wind power generation is also animportant factor to be taken into consideration. Therefore, based on real-time ambient conditions withactual line loading and with the help of IEEE-738-2006 standard, the conductor temperature is alsocalculated in this project.At the end, an economic analysis is performed to evaluate the financial advantages related to applying thedynamic line ratings approach in place of traditional static line ratings technique across an overheadconductor (VL3) and to know how much beneficial it is to temporarily postpone the rebuilding and/orconstruction of a new transmission line. Furthermore, an economic analysis related to wind power systemis taken into consideration as well to get familiar with the costs related to building and connecting a 60MW wind farm with the regional grid.

Place, publisher, year, edition, pages
2013. , 68 p.
EES Examensarbete / Master Thesis, XR-EE-ETK 2013:002
Keyword [en]
Regional grid, overhead conductor, wind power, real-time weather, dynamic line rating, static line rating, line current, conductor temperature, ampacity upgrading, economics
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
URN: urn:nbn:se:kth:diva-123370OAI: diva2:625843
Educational program
Master of Science - Electric Power Engineering
2013-06-05, Alfvén Laboratory Seminar Room, Teknikringen 31, Stockholm, 15:04 (English)
Available from: 2013-07-03 Created: 2013-06-05 Last updated: 2013-07-03Bibliographically approved

Open Access in DiVA

fulltext(2185 kB)1217 downloads
File information
File name FULLTEXT01.pdfFile size 2185 kBChecksum SHA-512
Type fulltextMimetype application/pdf

Search in DiVA

By author/editor
Talpur, Saifal
By organisation
Electromagnetic Engineering
Electrical Engineering, Electronic Engineering, Information Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 1217 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 268 hits
ReferencesLink to record
Permanent link

Direct link