Experimental Analysis of Variable Capacity Heat Pump Systems equipped with a liquid-cooled frequency inverter
KTH, School of Industrial Engineering and Management (ITM), Energy Technology, Applied Thermodynamics and Refrigeration.
2013 (English)Independent thesis Advanced level (degree of Master (Two Years)), 20 credits / 30 HE creditsStudent thesis
Abstract [en]

Using an inverter-driven compressor in variable capacity heat pump systems has a main drawback, which is the extra loss in the inverter. The present experimental study aims to recover the inverter losses by using brine-cooled and water-cooled inverters, thereby improving the total efficiency of the heat pump system. In order to achieve this goal, a test rig with the air-cooled, water-cooled and brine-cooled inverters is designed and built, and a comparative analysis of the recovered heat, inverter losses and system performance is conducted when the compressor is driven by the water-cooled, brine-cooled and air-cooled inverters at three different switching frequencies for each inverter.

The experimental results show that the inverter losses as a magnitude and as a ratio of the total consumed power are lowest in the brine-cooled inverter and highest in the air-cooled one at all the compressor speeds and all the inverter switching frequencies. Moreover, the recovered energy varies between 45 and 125 (W) in the water-cooled inverter, which corresponds to 63 and 69 (%) of the inverter losses; while it varies between 61 and 139 (W) in the brine-cooled inverter, which corresponds to 79 and 90 (%) of the inverter losses. It is also proved that the improvement of the system coefficient of performance (COPsys) is almost the same when the water-cooled or the brine-cooled inverter is used and varies between 0.54 and 3 (%) in comparison with using the air-cooled one. Indeed, the total isentropic efficiency of the compressor is improved slightly when using the water-cooled inverter and little more when using the brine-cooled one at the same running conditions. In addition, the total isentropic efficiency of the compressor is improved by increasing the inverter switching frequency when any of the inverters is used.

The experimental results also show that cooling the inverter by the water, which comes out from the condenser, increases the maximum temperature of the base plate of the inverter about 10 °C which could cause a two-fold deterioration in the inverter median life in comparison with cooling the inverter by air. On the contrary, using the brine for cooling the inverter decreases the maximum temperature of the base plate of the inverter about 30 °C which could cause about a six-fold improvement in the inverter median life.

Place, publisher, year, edition, pages
2013. , 44 p.
EES Examensarbete / Master Thesis, EGI-2013-006MSC
Keyword [en]
inverter-driven compressor, liquid-cooled inverter, variable capacity heat pump, variable speed compressor
National Category
Energy Engineering
URN: urn:nbn:se:kth:diva-118742OAI: diva2:607801
Subject / course
Applied Thermodynamics
Educational program
Master of Science - Sustainable Energy Engineering
2013-01-25, ETT library, Brinellvägen 68, Stockholm, 09:30 (English)
Capacity-controlled Ground Source Heat Pump single-family dwellings
Available from: 2013-04-11 Created: 2013-02-25 Last updated: 2013-04-11Bibliographically approved

Open Access in DiVA

fulltext(8679 kB)1324 downloads
File information
File name FULLTEXT01.pdfFile size 8679 kBChecksum SHA-512
Type fulltextMimetype application/pdf

Search in DiVA

By author/editor
Ebraheem, Thair
By organisation
Applied Thermodynamics and Refrigeration
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 1324 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 338 hits
ReferencesLink to record
Permanent link

Direct link