Change search
ReferencesLink to record
Permanent link

Direct link
Experimental testing and development of CO2 compressors: Eksperimentell utprøving og utvikling av CO2 kompressorer
Norwegian University of Science and Technology, Faculty of Engineering Science and Technology, Department of Energy and Process Engineering.
2012 (English)MasteroppgaveStudent thesis
Abstract [en]

CO2 is a natural refrigerant and is well suitable in many cooling applications. It has been used within the refrigeration industry from the 1900s, but got replaced as the synthetic refrigerants got introduced. In 1990 these fluids were proved damaging to the ozone layer and got replaced by a new series of synthetic fluids, which later have shown to be harmful to the global climate and therefore bound with restrictions from the governments. In the early 1990s at Norwegian University of Science and Technology(NTNU), professor Gustav Lorentzen introduced the transcritical refrigeration process and reintroduced CO2 as a refrigerant with favourable properties. Now the use of CO2 in heat pump applications is wide spread, and competitive alternatives within most markets are presented. However, there are still areas of improvement, and at the laboratories of SINTEF and NTNU a rig is being installed meant to do experiments on high effect CO2 cooling systems, with a cooling capacity of 400kW and a compressor capacity of el 100kW. Currently the rig is placed in Lustenau Austria at Obrist Engineerings facility where a 100kW high efficient semi hermetic 6 cylinder single stage piston compressor is being tested. This compressor is a new development and a result of a cooperation between SINTEF and Obrist Engineering. The background for this development was the lack of single stage compressors able to deliver flow rates in the range of 10 to 90m3=h. For experiment purposes the losses in the reciprocating cycle were evaluated, where the overall isentropic efficiency is most defining for the energy efficiency, and also the defining value for the entirety of all losses in the compressor unit. The test campaign was conducted in different test series, where the test points were set by Obrist Engineering with background in a cooling application on a fishing vessel. 3 series were set, where a fixed pressure ratio of 65/30 bar, 110/30 bar and 80/20 bar was tested in experiments with varying motor speed from 800 - 3800 rpm and a constant superheat at 10K. As the executions showed, some of the test points were not able to be tested, because of lack of power supply in the local power grid, and the maximum input power was set to 94kW. Test results revealed a relatively high overall efficiency with values at 73.5% for a pressure ratio of 65/30 bar. Also for the two other pressure ratios the efficiency showed to be satisfying in comparison with on the shelf compressors commercially available to day. However, the test campaign revealed a high volumetric loss in high pressure ranges, which partly can be substantiated with a relatively high clearance volume due to the shear size of the cylinder. In addition, Pindicated for low speeds versus high speeds shows a possible too small valve area at discharge for the highest speeds.

Place, publisher, year, edition, pages
Institutt for energi- og prosessteknikk , 2012. , 120 p.
Keyword [no]
ntnudaim:7322, MIPROD Produktutvikling og produksjon, Energi-, prosess- og strømningsteknikk
URN: urn:nbn:no:ntnu:diva-19335Local ID: ntnudaim:7322OAI: diva2:566999
Available from: 2012-11-11 Created: 2012-11-10 Last updated: 2013-06-06Bibliographically approved

Open Access in DiVA

fulltext(15966 kB)2926 downloads
File information
File name FULLTEXT01.pdfFile size 15966 kBChecksum SHA-512
Type fulltextMimetype application/pdf
cover(184 kB)26 downloads
File information
File name COVER01.pdfFile size 184 kBChecksum SHA-512
Type coverMimetype application/pdf
attachment(3034 kB)123 downloads
File information
File name ATTACHMENT01.zipFile size 3034 kBChecksum SHA-512
Type attachmentMimetype application/zip

By organisation
Department of Energy and Process Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 2926 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 102 hits
ReferencesLink to record
Permanent link

Direct link