Dynamic Analysis of Fire Water Pump Module
Norwegian University of Science and Technology, Faculty of Engineering Science and Technology, Department of Structural Engineering.
2012 (English)MasteroppgaveStudent thesis
Abstract [en]

The thesis starts with a simple description of the system and some brief theory needed for the following analysis. Further a factory acceptance test is performed, this implies measurement of the dynamic response due to load generated by the system itself under normal operation and making sure the dynamic behaviour are within the acceptance criteria. The data from the test is used to point out some weaknesses in the design from a dynamical point of view and some potential ideas of improvement are presented. To introduce additional damping of some of the rotational equipment is the idea which is proceeded with. A great simplification in this thesis is that only transversal vibrations (the y-component of the vibrations) are considered after the factory acceptance test is performed. This results in less reliable quantities although the trends and the final conclusion remains correct. A comprehensive finite element analysis is carried out to study the effect of a passive damper solution. It turns out that passive dampers can limit the vibrations remarkably, but if the foundation gets too soft the vibrations will increase. The low frequency vibration however, is not affected much by the additional damping. Some important eigenfrequencies are also studied and put into consideration. A sensitivity analysis of the constant damping ratio in the finite element solver is also performed. In addition a more trivial analysis is performed to study the effect of an active damper solution. This solution seems to be less effective and does not influence the low frequencies considerably neither. It also introduces additional risk and weight to the system, which is highly undesirable. The thesis concludes that passive damping of the hydraulic power unit has favourable effects on the system. If the main goal is to reduce low frequency vibration it might not be an entirely satisfying solution.

Place, publisher, year, edition, pages
Institutt for konstruksjonsteknikk , 2012. , 92 p.
Keyword [no]
ntnudaim:8189, MTPROD produktutvikling og produksjon, Industriell mekanikk
URN: urn:nbn:no:ntnu:diva-18359Local ID: ntnudaim:8189OAI: diva2:566035
Available from: 2012-11-08 Created: 2012-11-08 Last updated: 2013-06-14Bibliographically approved

Open Access in DiVA

fulltext(13645 kB)2378 downloads
File information
File name FULLTEXT01.pdfFile size 13645 kBChecksum SHA-512
Type fulltextMimetype application/pdf
cover(1873 kB)26 downloads
File information
File name COVER01.pdfFile size 1873 kBChecksum SHA-512
Type coverMimetype application/pdf
attachment(1627 kB)44 downloads
File information
File name ATTACHMENT01.zipFile size 1627 kBChecksum SHA-512
Type attachmentMimetype application/zip

By organisation
Department of Structural Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 2379 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 115 hits
ReferencesLink to record
Permanent link

Direct link