Komfortkylsystems installationskostnader och energiförbrukning i kontor
Umeå University, Faculty of Science and Technology, Department of Applied Physics and Electronics.
2011 (Swedish)Independent thesis Advanced level (professional degree), 20 credits / 30 HE creditsStudent thesisAlternative title
Installation and energy costs for comfort cooling in offices (English)
Abstract [sv]

På uppdrag av Creanova AB har detta examensarbete genomförts under hösten 2010. Målet med examensarbetet var att analysera hur installations- och energikostnaderna för komfortkylsystem i standardkontor varierar med olika dimensionerande förutsättningar. Förutsättningarna som har undersökts är framförallt dimensionerande inomhustemperatur, men även solskydd i form av lameller och persienner samt LED-belysning har undersökts. Alla varierade parametrar har simulerats i fyra olika väderstreck både med CAV(Constant Air Volume)-system med konventionell tilluftsbaffel och VAV(Variable Air Volume)-system med LindInvents aktiva tilluftsdon TTD-160.

Beräkningarna för kontoren har simulerats i klimatsimuleringsprogrammet IDA ICE 4.0. Därefter projekterades två olika systemlösningar för kontoret, en med CAV-lösning samt en med VAV-lösning. Slutligen beräknades installationskostnaderna för varje simulering samt dess energiförbrukning.

Beräkningarna visar att komfortkylans installationskostnader för ett kontorslandskap ökar med ca 50 % då den dimensionerande inomhustemperaturen sänks från 26 till 22°C för CAV-systemet med tilluftsbafflar. Motsvarande siffra för VAV-systemet med tilluftsdon är ca 40 %. Energikostnaden för komfortkyla och värme ökar med ca 114 % för CAV-systemet och ca 127 % för VAV-lösningen då samma dimensionerande temperatursänkning genomförs.

Genom att montera olika typer av solskydd på kontorets fönster kan kylbehovet för kontor med syd-, öst-, eller västfasad reduceras kraftigt, vilket tydligt avspeglas i kostnaderna både för installationer och för energi. Kontor med nordfasad är ej nödvändigt att avskärma, då nordfasader redan har väldigt låg solinstrålning.

Installationskostnaderna för VAV-lösningen har enligt beräkningarna visat sig vara ca 10-15 % lägre än motsvarande CAV-lösning med samma förutsättningar och energikostnaden för VAV-lösningen är mellan 20-27 % lägre än för CAV-lösningen.

Men att projektera VAV-system lämpar sig inte alltid, då kanaler och installationer tar större plats p.g.a. ventilationskanalernas ökade storlek. Vid väldigt exklusiva byggnader kan det inträffa att ventilationskanalernas ökade schaktyta innebär att de förlorade hyresintäkterna är större än den besparing som den sänkta energiförbrukningen genererar.

Abstract [en]

On behalf of Creanova AB this master thesis has been implemented in the autumn 2010. The aim with the project was to analyze how installation and energy costs for comfort cooling in office buildings depends on different design conditions. The conditions that have been examined is particularly the design indoor temperature, but also sun protection in terms of louvers and blinds as well as LED lighting.

All the varied parameters have been simulated in four different directions with both CAV (Constant Air Volume) systems with conventional baffle and VAV (Variable Air Volume) systems with active diffuser TTD-160 from Lindinvent.

The calculations for the office have been simulated in climate simulation program IDA ICE 4.0. After that two different solutions were developed for the office, one with CAV ventilation and one with VAV ventilation. Finally installation cost of each simulation and its energy consumption was calculated.

The calculations show that the installation costs for an office space will increase by about 50% when the design indoor temperature is lowered from 26 to 22 ° C for the CAV system with supply air baffle. The corresponding figure for the VAV system with inlet diffuser is about 40%. Energy costs for air conditioning and heating will increase by about 114% for the CAV system and approximately 127% for VAV solution in which the same design temperature drop is implemented.

By attaching different types of sunscreen on the office window, the need for comfort cooling for offices with south, east, or west facade is greatly reduced, which is clearly reflected in the costs for both installation and energy. To attach sunscreen on offices with north facades are not necessary, because the solar radiation on north facades is already very low. The installation costs for the VAV solution has proven to be about 10-15% lower than the CAV solution with the same conditions and energy costs for the VAV solution is between 20-27% lower than for the CAV solution

But designing VAV systems are not always appropriate, since the ducts and installations take up more space because of the ventilation ducts increased size. When very exclusive buildings are constructed the ventilation ducts increased shaft area may lead to that the lost rental income is greater than the savings that the lower energy consumption generates.

Place, publisher, year, edition, pages
2011. , 74 p.
Series
EN11
National Category
Energy Engineering
Identifiers
URN: urn:nbn:se:umu:diva-58967OAI: oai:DiVA.org:umu-58967DiVA: diva2:550439
External cooperation
Creanova AB
Educational program
Master of Science Programme in Energy Engineering
Uppsok
Technology
Supervisors
Examiners
Available from: 2012-09-07 Created: 2012-09-07 Last updated: 2012-09-07Bibliographically approved

Open Access in DiVA

fulltext(2746 kB)570 downloads
File information
File name FULLTEXT01.pdfFile size 2746 kBChecksum SHA-512
6fb6bc2ad0a78d620c1667f4a172e90cbd95336b357733668fa8c72e1f2fdcf72dc24be324fbbe4c4f7085d78fbba39c5537bbaca17818d6aaae33e1dd1a272b
Type fulltextMimetype application/pdf

By organisation
Department of Applied Physics and Electronics
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 570 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 346 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf