Fjärrvärmeanslutna passivhus: Fallstudie av värmelaster och innetemperaturer i fyra flerbostadshus
Halmstad University, School of Business and Engineering (SET).
2012 (Swedish)Independent thesis Advanced level (degree of Master (One Year)), 10 credits / 15 HE creditsStudent thesis
Abstract [sv]

Intresset kring lågenergibyggnader blir allt större och så kallade passivhus, med god isolering, hög lufttäthet och värmeåtervinning, byggs i allt större utsträckning i Sverige och andra europeiska länder. Vissa frågetecken har dock uppkommit kring inomhusklimatet i husen och risken för både under- och övertemperaturer. En annan viktig aspekt är hur husens egenskaper påverkar värmelasterna och hur detta i sin tur påverkar energiförsörjningssystemet. I detta examensarbete undersöks dessa båda aspekter – värmelastegenskaper och innetemperaturer – i fyra likadana nybyggda flerbostadshus i Falkenberg. Mätvärden från husens tekniska system, inklusive lufttemperaturmätningar i samtliga lägenheter, analyseras. Husen består av totalt 108 lägenheter, värms med fjärrvärme och använder ca 50 kWh/m2 Atemp årligen.

Värmelastegenskaperna kännetecknas framförallt av låga effektbehov för både uppvärmning och varmvatten samt relativt stora svängningar över dygnet. Husen tycks vara känsligare för variationer i interntillskott än konventionella hus, vilket leder till regelbundna svängningar i effektbehovet för uppvärmning, med en topp under natten och morgonen. Detta leder till förstärkta svängningar i fjärrvärmenätet, vilket skulle kunna undvikas med hjälp av effektstyrning. Passivhusens stora termiska tröghet talar för en sådan möjlighet.

Även innetemperaturen uppvisar regelbundna dygnsvariationer, som kan vara något större än i vanliga hus. Låga temperaturer förekommer tidvis under vintern, men resultaten pekar inte på några brister i de tekniska systemen. Temperaturen på sommaren är inte högre än i andra hus, och övertemperaturer tycks inte vara något stort problem i dessa hus. Det kan dock finnas en möjlighet att minska risken för övertemperaturer ytterligare genom användning av nattkyla under varma perioder. Denna möjlighet kan vara ett sätt att utnyttja passivhusens speciella egenskaper för att ytterligare förbättra konceptet.

Abstract [en]

There is today an increasing interest in low-energy buildings, and the so-called “passive houses” are becoming increasingly popular in Sweden and other European countries. There are however some concerns regarding the indoor climate in these houses, notably the risk of too low indoor temperatures in the winter and too high temperatures in the summer. Another issue is the heat load characteristics of this type of buildings, and how these affect the energy systems. In this thesis, these two aspects – heat load characteristics and indoor temperatures – are analysed in four identical multi-family buildings in Falkenberg, Sweden, using measured values from the buildings’ technical systems and measured indoor air temperatures in all dwellings. The buildings are heated with district heating, comprise 108 dwellings in total and use approximately 50 kWh/m2 annually (space heating, hot water and electricity for building services).

The heat loads are mainly characterised by low but varying heat demands for space heating and hot water. The buildings appear to have a higher than usual sensitivity for variations in heat from internal sources and solar gains, leading to regular variations in the heat demand for space heating and fluctuations in the total heat demand. These fluctuations, which may negatively affect the energy system, could be avoided by actively controlling the heat demand for space heating.

There are also daily fluctuations in the indoor temperatures, but the buildings perform well in this aspect, with temperatures that stay within the acceptable range most of the time. The summer indoor temperatures do not get higher than in other buildings. A possibility for further improvement within this area could be the use of forced ventilation during the night in hot periods, and hence utilising the buildings’ well insulated and airtight building envelope to keep heat out during the day. This possibility might further improve the passive house concept.

Place, publisher, year, edition, pages
2012. , 64 p.
Keyword [en]
low-energy houses, passive houses, district heating, heat load characteristics, indoor temperature, indoor climate
Keyword [sv]
lågenergihus, passivhus, fjärrvärme, värmelast, innetemperatur, inomhusklimat
National Category
Energy Engineering
Identifiers
URN: urn:nbn:se:hh:diva-17750OAI: oai:DiVA.org:hh-17750DiVA: diva2:529581
Subject / course
Energy Technology
Uppsok
Technology
Supervisors
Examiners
Available from: 2012-06-19 Created: 2012-05-29 Last updated: 2012-06-19Bibliographically approved

Open Access in DiVA

Fjärrvärmeanslutna passivhus(3072 kB)729 downloads
File information
File name FULLTEXT01.pdfFile size 3072 kBChecksum SHA-512
9c76c16b8fded574dd23b9797de2c4fd237141a080ff521956d167675e8dc7e24aa006445ce25b3e4c8a90f09079a9e57b5b0beaf4cfcec1e0b035be9a9fc9a6
Type fulltextMimetype application/pdf

By organisation
School of Business and Engineering (SET)
Energy Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 729 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 655 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf