Gotland as a microgrid -  Energy storage systems frequency response in grids with high level of renewable energy penetration
Uppsala University, Disciplinary Domain of Science and Technology, Technology, Department of Engineering Sciences, Electricity.
2018 (English)Independent thesis Advanced level (degree of Master (Two Years)), 20 credits / 30 HE creditsStudent thesis
Abstract [en]

The Swedish island of Gotland , situated about 100 km from mainland Sweden in the Baltic Sea, represents a power system with a high wind power penetration. The island is connected to the mainland Sweden exclusively via two HVDC cables that provide the only source of active power and frequency control. The two cables can operate in different configurations, i.e. import or export power from or to mainland. However, in order to ensure the N-1 criterion, one of the cables currently always must import power from the mainland. This means that the available power exporting capacity is limited to the rated power of one of the cables. Therefore, in the case of having a fault on the exporting HVDC cable during low load demand and high wind power production, the power system will suffer from high active power transients that will increase the frequency above the acceptable threshold. Consequently, the protection system will trip the over-frequency relays, triggering cascading outages on the island that might eventually lead to blackout if the problem is not addressed correctly. Thus, increasing the renewable energy production on Gotland is currently considered as a risk that will increase the probability of instable over-frequency contingencies. This has led the local grid operator to cap the installed wind power capacity to its current level. Therefore, the ability to preserve the stability of the power system during islanded operations until the HVDC cables fault is cleared or the emergency reserves are online is essential for the growth of installed wind power capacity.

The main objective of the thesis is to examine the capability of a centralized energy storage along with or without wind curtailment. The ESS is tested for maintaining the frequency stability during the unintentional islanding through dynamic studies using the software PSS/E. The results show that an ESS prevents frequency instabilities and provide frequency response during HVDC cables fault albeit of the absence of any form of rotating inertia. The results show that for today’s 185 MW of installed wind power capacity, an energy storage of 50 MW power capacity will reduce over-frequency instabilities in the case of HVDC cables fault from 13% to 1%. The analysis finds that the power capacity of the energy storage depends on the exported power from the HVDC cables at the instant of fault, which eventually relates to the installed wind power capacity. finally, the study shows that using wind power curtailment will significantly decrease the energy capacity of the energy storage.

Place, publisher, year, edition, pages
2018.
Series
TVE-MFE ; 18002
Keywords [en]
Energy Storage System, Frequency Response, Gotland, Microgrid, Wind Curtailment, PSS/E
National Category
Electrical Engineering, Electronic Engineering, Information Engineering
Identifiers
URN: urn:nbn:se:uu:diva-354132OAI: oai:DiVA.org:uu-354132DiVA, id: diva2:1220773
Educational program
Master Programme in Renewable Electricity Production
Supervisors
Examiners
Available from: 2018-06-19 Created: 2018-06-19 Last updated: 2018-06-19Bibliographically approved

Open Access in DiVA

fulltext(4517 kB)39 downloads
File information
File name FULLTEXT01.pdfFile size 4517 kBChecksum SHA-512
3a4e33fce0c09fe2308d3bbc41fabc5dd2b4ff2dc1b8d76e27552a021f83feee3787f23aae4fb927f8d376999599e26b9371ee38b92006a88d21c78fbdee5f8e
Type fulltextMimetype application/pdf

By organisation
Electricity
Electrical Engineering, Electronic Engineering, Information Engineering

Search outside of DiVA

GoogleGoogle Scholar
Total: 39 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

urn-nbn

Altmetric score

urn-nbn
Total: 243 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf