Analys av en spänningshöjning på ett mellanspänningsnät
Halmstad University, School of Business, Engineering and Science.
Halmstad University, School of Business, Engineering and Science.
2017 (Swedish)Independent thesis Basic level (degree of Bachelor), 10 credits / 15 HE creditsStudent thesisAlternative title
Analysis of an increased voltage level on a mediumvoltage grid (English)
Abstract [sv]

Denna rapport analyserar följderna av en spänningshöjning i ett mellanspänningsnät från 6 kV till12 kV alternativt till 20 kV. Rapporten undersöker ett befintligt elnät i södra Sverige som ägs avMellersta Skånes Kraft ek. För. (MSK). Det består av 177 stycken transformatorer, har ca 2500kunder och överförde totalt runt 32 GWh år 2016.Rapporten är uppdelad i tre delar, den första delen behandlar de tekniska aspekterna av en förhöjdspänningsnivå, den andra delen behandlar de ekonomiska följderna detta kan medföra och dentredje delen presenterar slutsats och diskussion.Elnätet simulerades i programvaran Neplan och elektriska beräkningar utfördes på olika driftfallunder årets månader. Lasterna i nätet fastställdes bland annat genom att använda Velandersmetod. Information och indata av nätets komponenter inhämtades genom produktblad, kontaktmed tillverkare och MSK samt genom diverse litteratur.Rapporten visar att en ökad spänningsnivå i elnätet minskade transmissionsförlusterna ochmedförde lägre kostnader för elnätföretaget. Det medförde också andra tekniska fördelar,exempelvis att spänningsfallet minskade, belastningsgraden av nätets komponenter minskade samtatt kortslutningsströmmen blev lägre. En högre spänningsnivå ökade nätets generering av reaktiveffekt.Elnätföretagets intäktsram förändras vid en förhöjd spänningsnivå, dels till följd av det tillägg somerhålls vid effektivt utnyttjande av elnät, dels då vissa anläggningsdelar i nätet ersätts. Lönsamheteni att investera inför en ökad spänningsnivå berodde på flera faktorer, bland annat vilka typer avanläggningsdelar som behövde ersättas, kapitalstrukturen på investeringen och elnätföretagetskalkylränta. I lönsamhetsanalysen använder rapporten internräntemetoden.I fallet för MSK antogs samtliga av elnätets transformatorer behöva ersättas vid en ökadspänningsnivå, vilket således ökade intäktsramen inför nästa tillsynsperiod med totalt ca 3,4 Mkr.Internräntan för investeringen bestämdes till 4,62%. En viss osäkerhet råder dock kring ett antalav elnätets olika anläggningsdelar (kablar, ledningar och transformatorer) vilket kan påverkainvesterings omfattning, utfall och om nätet kan hantera en förhöjd spänningsnivå i sitt nuvarandeskick.

Abstract [en]

This report analyses the consequences of an increased voltage level in a medium voltage gridfrom 6 kV to 12 kV alternatively to 20 kV. The report examines an existing electricity grid insouthern Sweden, owned and operated by the power company Mellersta Skånes Kraft ek. För.(MSK). It consists of 177 transformers, has approximately 2500 customers and transferred 32GWh (incl. losses) in 2016.The report is divided into three parts, the first part addresses the technical aspects of an increasedvoltage level, the second part addresses the economic consequences that this implies and thethird part presents the conclusion and discussion.The grid was simulated in Nepal software and electrical calculations were performed on 12different operating modes, one for each month of the year. The loads in the network weredetermined by using Velander's method. Information and input-data of network componentswere obtained through product sheets, direct contact with manufacturers and MSK and as wellas through various literature.The report shows that an increased voltage level in the grid reduced transmission losses andresulted in lower costs for the grid owner. It also brought other technical benefits, such as lowervoltage drops, lower load intensity of network components, and lower short circuit current. Ahigher voltage level increased the network's generation of reactive power.The grid company’s revenue frame changes with an increased voltage level, partly because of thebonus that is obtained through efficient utilization of the grid, partly by replacing certaincomponents in the grid. The profitability of investments imposed by an increased voltage levelquickly became complicated due to several factors. Including what type of components thatneeded replacement, the capital structure of the investment and the electricity company's rate ofinterest. In the profitability analysis, the report uses the internal rate of return method.In the case of MSK it was assumed that all the power grid transformers needed replacement withan increased voltage level, thus increasing the revenue frame for the next supervisory period byapproximately 3.4 million SEK. The internal rate of return for the investment was found at 4.62%.However, some uncertainty exists about several components (cables, wires and transformers) inthe grid, which may affect the profitability of the investment and the grid’s capability to handle anincreased voltage level in its present state.

Place, publisher, year, edition, pages
2017. , 28 p.
Keyword [sv]
Spänningshöjning, spänning, elkraft, elkraftsystem, lokalnät, distributionsnät, elnät, mellanspänning
National Category
Energy Systems
Identifiers
URN: urn:nbn:se:hh:diva-33974OAI: oai:DiVA.org:hh-33974DiVA: diva2:1105543
External cooperation
ÅF Power Distribution, Halmstad; Mellersta Skånes Kraft Ek. För.
Subject / course
Energy Technology
Supervisors
Examiners
Available from: 2017-06-05 Created: 2017-06-04 Last updated: 2017-06-05Bibliographically approved

Open Access in DiVA

fulltext(11342 kB)38 downloads
File information
File name FULLTEXT02.pdfFile size 11342 kBChecksum SHA-512
dcc9ea748e57d0574f70c6cef4dc6ada25e7d15de7d4dca1022eaa2280fac445cdc878322ea9ca29a52bbab21d0fd201241273540be7d69ffeb6bca484c45801
Type fulltextMimetype application/pdf

By organisation
School of Business, Engineering and Science
Energy Systems

Search outside of DiVA

GoogleGoogle Scholar
Total: 38 downloads
The number of downloads is the sum of all downloads of full texts. It may include eg previous versions that are now no longer available

Total: 81 hits
CiteExportLink to record
Permanent link

Direct link
Cite
Citation style
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Other style
More styles
Language
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Other locale
More languages
Output format
  • html
  • text
  • asciidoc
  • rtf