Open this publication in new window or tab >>Show others...
2018 (English)In: IEEE transactions on energy conversion, ISSN 0885-8969, E-ISSN 1558-0059, Vol. 33, no 1, p. 59-67Article in journal (Refereed) Published
Abstract [en]
The static exciter is dominating among large grid-connected generators due to the weak dynamic performance of conventional brushless exciters. In this paper, a six-phase outer pole permanent magnet rotating brushless exciter is evaluated with different active rectification topologies. Both thyristor-based and chopper-based topologies are considered. A fast-response brushless excitation system is obtained by replacing the conventional rotating diode bridge rectifier with the proposed active rectification topologies on the shaft. The given two-stage system generates its own excitation power directly from the shaft, contrary to static exciters. The selection of an appropriate rectification topology could minimize the rotor armature phase currents for a given generator field current. The objective is a high power factor and a high utilization of the exciter machine. An optimal rectification topology makes higher ceiling currents possible, improving the transient behavior of the synchronous generator. In this paper we show that six-phase topologies add complexity, but improve exciter redundancy, increase the available ceiling voltage and reduce the steady state torque ripple. Experimental results are given for validating the models implemented for the analysis.
National Category
Other Electrical Engineering, Electronic Engineering, Information Engineering
Research subject
Engineering Science with specialization in Science of Electricity
Identifiers
urn:nbn:se:uu:diva-328396 (URN)10.1109/TEC.2017.2746559 (DOI)000425623700007 ()
2017-08-222017-08-222018-04-25Bibliographically approved