An investigation on energy consumption of air conditioning system in Beijing subway stations
Visa övriga samt affilieringar
2017 (Engelska)Ingår i: Energy Procedia, ISSN 1876-6102, E-ISSN 1876-6102, Vol. 142, s. 2568-2573Artikel i tidskrift (Refereegranskat) Published
Abstract [en]

This paper initially depicted on the energy consumption of air conditioning systems in Beijing subway stations. An investigation was conducted among ten underground subway stations to the examination of practical operation conditions of their cooling units. The overall field testing included information such as air conditioning system formation, equipment types, system operation parameters, energy consumption and system operation efficiency. The results showed that the COP value of refrigerators in the tested subway stations were generally high at about 4.4 in average. Nevertheless, the mean EER and SCOP values were nearly 27% and 48% lower than the average COP value due to the large amount of energy consumption in water pumps, cooling towers and fans. There was a big difference among each station in terms of the instantaneous power consumption of air conditioning systems. The most energy consuming station was nearly seven times higher than the least one. It was observed that there was a lack of maintenance and system operation strategy for these underground air condition systems. A promising potential for energy saving was found out within the air conditioning systems in Beijing subway stations.

Ort, förlag, år, upplaga, sidor
2017. Vol. 142, s. 2568-2573
Nyckelord [en]
subway station, air conditioning system, energy consumption
Nationell ämneskategori
Energisystem Samhällsbyggnadsteknik
Forskningsämne
Energi, skog och byggd miljö
Identifikatorer
URN: urn:nbn:se:du-27279DOI: 10.1016/j.egypro.2017.12.093ISI: 000452901602111Scopus ID: 2-s2.0-85041545922OAI: oai:DiVA.org:du-27279DiVA, id: diva2:1184798
Konferens
9th International Conference on Applied Energy, ICAE 2017; Cardiff; United Kingdom; 21-24 August 2017
Tillgänglig från: 2018-02-22 Skapad: 2018-02-22 Senast uppdaterad: 2019-01-07Bibliografiskt granskad

Open Access i DiVA

fulltext(1020 kB)94 nedladdningar
Filinformation
Filnamn FULLTEXT02.pdfFilstorlek 1020 kBChecksumma SHA-512
ad01fbddd8de596d784b40f52e747f9406c3efb61c982e6ecd5c0ae2d5b5182f00de82e6b591da0054f4348601c879207b9cd2e55f20b13f2e9ccc84a7f33199
Typ fulltextMimetyp application/pdf

Övriga länkar

Förlagets fulltextScopus

Sök vidare i DiVA

Av författaren/redaktören
Zhang, Xingxing
Av organisationen
Energiteknik
I samma tidskrift
Energy Procedia
EnergisystemSamhällsbyggnadsteknik

Sök vidare utanför DiVA

GoogleGoogle Scholar
Totalt: 160 nedladdningar
Antalet nedladdningar är summan av nedladdningar för alla fulltexter. Det kan inkludera t.ex tidigare versioner som nu inte längre är tillgängliga.

doi
urn-nbn

Altmetricpoäng

doi
urn-nbn
Totalt: 135 träffar
RefereraExporteraLänk till posten
Permanent länk

Direktlänk
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annat format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annat språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf