Högfrekventa övertoner i sjukvårdens elnät – utvärdering av skillnader i tid och rum
Umeå universitet, Teknisk-naturvetenskapliga fakulteten, Institutionen för tillämpad fysik och elektronik.
2016 (svensk)Independent thesis Basic level (professional degree), 10 poäng / 15 hpOppgaveAlternativ tittel
High frequency harmonics in the healthcare power grid – evaluation of differences in time and space (engelsk)
Abstract [sv]

Examensarbetet går ut på att utreda hur störningsnivån varierar över tid i elnätet samt ett antal olika ställen inom Norrlands universitetssjukhus, Umeå. Elektrisk fältmätning ingick också i arbetet för att undersöka om det fanns ett samband mellan det elektriska fältet och övertoner i sjukhusets elnät.

Examensarbetet presenterar grundläggande teori om elnät, elkvalité och parametrar som beskriver elkvalité, t.ex. övertoner, flimmer och transienter. Förslag på hur övertonshalten kan reducera tas även upp.

Mätningarna av elkvalitets parametrar genomfördes med ett antal mätinstrument. Insamlat mätdata analyserades i några olika programvaror.

Undersökningen visar att övertonshalten varierade mycket över dygnet och var högst på intensivvårdsavdelning där maxvärdet på spänningsövertonshalten THDu var 4,01%. Ström, spänning och frekvens var inte stabila, dvs. transienter och flimmer har uppstått under mätningen. Analysen av mätdata visar att den totala spänningsövertonshalten THDu var under 5% och inte överskred gränsvärdet 8% som anges i standarden SS-EN 50 160.

Abstract [en]

The aim of the thesis was to examine whether the level of disturbance in the power grid vary between different types of care environment over time at University Hospital of Umeå. Electric field measurement was also included in the thesis to investigate whether there was a connection between the electric field and harmonics in the hospital’s power grid.

The thesis presents basic theory about power grid, power quality and parameters which describe power quality, such as, harmonics, flicker and transients. Suggestions on how to reduce the harmonic content will also be discussed.

The measurements of the power quality parameters were performed by using different measuring equipment. The data were analyzed using different software.

The study shows that the harmonic content often varied and was highest in intensive care unit, where the maximum value of the harmonic voltage distortion THD was 4,01%. The measurement shows that current, voltage and frequency were not stable, that is transients and flicker occurred several times during the measurement. The analysis of the data shows that the harmonic voltage distortion THDu was below 5% and never above the limit 8% which is specified in the standard SS-EN 50 160. 

sted, utgiver, år, opplag, sider
2016. , s. 22
Emneord [en]
distortion, harmonics, power grid, hospital
Emneord [sv]
störningar, övertoner, elnät, NUS, Norrlands universitetssjukhus
HSV kategori
Identifikatorer
URN: urn:nbn:se:umu:diva-122510OAI: oai:DiVA.org:umu-122510DiVA, id: diva2:939356
Eksternt samarbeid
Medicinsk Teknik, Forskning och utveckling - NUS
Fag / kurs
Elektronik
Utdanningsprogram
Bachelor of Science Programme in Electronic and Computer Engeneering/ Medical engineering
Veileder
Examiner
Tilgjengelig fra: 2016-06-19 Laget: 2016-06-19 Sist oppdatert: 2016-06-19bibliografisk kontrollert

Open Access i DiVA

fulltext(1113 kB)273 nedlastinger
Filinformasjon
Fil FULLTEXT01.pdfFilstørrelse 1113 kBChecksum SHA-512
b3bc6784a4fa254e1891176a2caa46352d97e12c3525a56edee1ccad2729857984ee71cbe158131d0cf33da5100aa3bbea123fd5605e0cccca9c678b3eb0a9f1
Type fulltextMimetype application/pdf

Av organisasjonen

Søk utenfor DiVA

GoogleGoogle Scholar
Totalt: 273 nedlastinger
Antall nedlastinger er summen av alle nedlastinger av alle fulltekster. Det kan for eksempel være tidligere versjoner som er ikke lenger tilgjengelige

urn-nbn

Altmetric

urn-nbn
Totalt: 98 treff
RefereraExporteraLink to record
Permanent link

Direct link
Referera
Referensformat
  • apa
  • ieee
  • modern-language-association-8th-edition
  • vancouver
  • Annet format
Fler format
Språk
  • de-DE
  • en-GB
  • en-US
  • fi-FI
  • nn-NO
  • nn-NB
  • sv-SE
  • Annet språk
Fler språk
Utmatningsformat
  • html
  • text
  • asciidoc
  • rtf